Input Voltage |
: |
As specified by customer with +/- tolerance (1 ph or 3 ph – 3 wire/ 4 wire, 50Hz / 60Hz
+/-5%). |
Nominal DC Voltage |
: |
12V / 24V / 48V / 110V / 125V / 220V / 360V DC or as per Customer’s requirement. |
DC Output Current |
: |
Upto 3000A DC or as per customer’s / system requirement. |
DC Vtg. Regulation |
: |
+/-1% |
Current Limit |
: |
103% Rated Current |
Output Ripple |
: |
Less than or Equal to 1% RMS without battery connected. |
Efficiency |
: |
80 to 93% at maximum output parameters & at Nominal AC I/P Voltage. |
Standard Protection |
: |
Soft Start Feature, SCR Fuse Protection, Current Limit, Phase Failure and Phase Sequence
Reversal. |
Standard Alarms |
: |
Mains Fail, DC Over voltage, DC Under voltage, Rectifier Fuse blown. |
Standard Metering |
: |
Output DC Voltage & Out DC Current. |
Cooling |
: |
Natural / Forced Air cooled (as per customer’s requirement) |
Enclosure Protection |
: |
IP20 / IP31 / IP42 (as per customer’s / site requirement) |
Operating Temp. |
: |
0 – 50 deg C. |